Systems, the PowerFlex 400 AC drive offers a wide range of built-in features allowing for seamless HVAC building system integration. The PowerFlex 400 is. PowerFlex 400 User Manual, publication 22C-UM001 PowerFlex 400 AC Drive www.klinkmann.com 6 / 2011. 380.480V AC, Three-Phase Drives Drive Ratings. PowerFlex 527 AC Drives. Our PowerFlex® 527 AC Drives are designed to work exclusively with our Logix Programmable Automation Controllers (PACs). This allows the drive to leverage the capabilities of the controller and use Studio 5000 Logix Designer™ to help simplify machine development and use. Manual Conventions In this manual we refer to the PowerFlex 70 Adjustable Frequency AC Drive as; drive, PowerFlex 70 or PowerFlex 70 Drive. To help differentiate parameter names and Liquid Crystal Display (LCD) text from other text, the following conventions are used:. Parameter Names appear in brackets. For example: DC Bus Voltage. Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual. Advanced display group parameters. Rockwell Automation Equipment.

Advertising

PowerFlex 400 Adjustable Frequency AC Drive FRN 4.xx This Quick Start guide summarizes the basic steps needed to install, start-up and program the PowerFlex 400 Adjustable Frequency AC Drive. The information provided Does Not replace the User Manual and is intended for qualified drive service personnel only. Learn the basics of drive configuration and programming using the PowerFlex 525 compact AC drive and the PowerFlex 755 AC Drive. Attendees will configure these drives using the Human Interface Module (HIM), Connected Components Workbench software and Studio 5000™ Logix Designer software. PowerFlex 400 Adjustable Frequency AC Drive Quick Start. To clear a fault, press the Stop key, cycle power or set A100 Fault Clear to 1 or 2. For a complete listing of Faults and Alarms, refer to the PowerFlex 400 User Manual.

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-25

To clear a fault, press the Stop key, cycle power or set A100 [Fault Clear] to 1 or
2.

For a complete listing of Faults and Alarms, refer to the PowerFlex 400
User Manual.

Fault Codes

No.

Fault

Description

F2

Auxiliary Input

(1)

Check remote wiring.

F3

Power Loss

Monitor the incoming AC line for low voltage or line power interruption.

F4

UnderVoltage

(1)

Monitor the incoming AC line for low voltage or line power interruption.

F5

OverVoltage

(1)

Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be
caused by motor regeneration. Extend the decel time or install a dynamic brake chopper.

F6

Motor Stalled

(1)

Increase [Accel Time x] or reduce load so drive output current does not exceed the current set
by parameter A089 [Current Limit].

F7

Motor Overload

(1)

An excessive motor load exists. Reduce load so drive output current does not exceed the
current set by parameter P033 [Motor OL Current].

F8

Heatsink OvrTmp

(1)

Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded 40

°

C

(104

°

F) for IP 30/NEMA 1/UL Type 1 installations or 50°C (122°F) for Open type installations.

Check fan.

F12

HW OverCurrent

Check programming. Check for excess load, improper DC boost setting, DC brake volts set too
high or other causes of excess current.

F13

Ground Fault

Check the motor and external wiring to the drive output terminals for a grounded condition.

Ac Drive Motors

F15

Dreadbox abyss manual download. Load Loss

Check for load loss (i.e., a broken belt).

F29

Analog Input Loss

(1)

An analog input is configured to fault on signal loss. A signal loss has occurred.

F33

Auto Rstrt Tries

Correct the cause of the fault and manually clear.

F38

Phase U to Gnd

Check the wiring between the drive and motor. Check motor for grounded phase.
Replace drive if fault cannot be cleared.

F39

Phase V to Gnd

F40

Phase W to Gnd

F41

Phase UV Short

Check the motor and drive output terminal wiring for a shorted condition.
Replace drive if fault cannot be cleared.

F42

Phase UW Short

F43

Phase VW Short

F48

Params Defaulted

The drive was commanded to write default values to EEPROM. Clear the fault or cycle power to
the drive. Program the drive parameters as needed.

F63

SW OverCurrent

(1)

Check load requirements and A098 [SW Current Trip] setting.

F64

Drive Overload

Reduce load or extend Accel Time.

F70

Powerflex 400 Manual Pdf

Power Unit

Cycle power. Replace drive if fault cannot be cleared.

F71

Net Loss

The communication network has faulted.

F81

Comm Loss

If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port
expander, adapters or complete drive as required. Check connection. An adapter was
intentionally disconnected. Turn off using C105 [Comm Loss Action].

F94

Function Loss

Close input to terminal 01 and re-start the drive.

Jetboil zip cooking system user manual. Also be sure to check out the to learn more about the features of this backcountry stove! That’s why I bought a (PCS). Note, the JetBoil Flash is the newer version of the JetBoil PCS.It is relatively lightweight, very compact, and easy to set up. What more could I ask for?In the following series of 3 videos, I demonstrate how to use a JetBoil Personal Cooking System.

F100 Parameter Checksum Restore factory defaults.
F122 I/O Board Fail

Cycle power. Replace drive if fault cannot be cleared.

What Is An Ac Drive

(1)

Auto-Reset/Run type fault. Configure with parameters A092 and A093.